
Home › Knowledge Hub › Winter Preparedness › Ventilation and Indoor Air Quality in Aged Care
Winter Preparedness
By Lyndon Forrest, Managing Director · Clinically reviewed by Bridgette Mackie & Dianne Newey, Clinical Directors · July 2026 · Updated November 2026 · 11 min read
Ventilation and Indoor Air Quality in Aged Care
TL;DR —
Ventilation and indoor air quality are critical, yet frequently overlooked, components of infection prevention in aged care. Respiratory infections (influenza, COVID-19, RSV) transmit via aerosols that accumulate in poorly ventilated indoor spaces. CO2 monitoring is a practical, low-cost indicator of how well a room is ventilated for its occupancy. Many facilities use about 800 ppm as an action trigger for communal areas, although Australian authorities do not set a single CO2 limit for aged care. Facilities should complete HVAC maintenance, filter replacement, and CO2 monitor calibration before winter. Portable HEPA air purifiers supplement mechanical ventilation in high-risk areas during outbreaks. The challenge in aged care is balancing ventilation (which requires air exchange) with thermal comfort for elderly residents who are vulnerable to cold. Under the Strengthened Aged Care Quality Standards (effective 1 November 2025), residential providers must provide a safe, clean and comfortable service environment and have an effective IPC system (Standard 4, Outcome 4.2). Ventilation is part of managing that environment, although the Standards do not set ventilation rates.

How Do Respiratory Infections Spread via Aerosols and Droplets?
Respiratory infections in aged care spread through three primary routes: large droplets, aerosols (fine respiratory particles), and contact with contaminated surfaces (fomites). The COVID-19 pandemic confirmed that aerosol transmission plays a more significant role in respiratory infection spread than previously recognised.
Large droplets (larger than 100 micrometres): produced by coughing, sneezing and talking. They fall quickly, usually within 1 to 2 metres, and land on surfaces or on people nearby. Surgical masks, distance and cleaning address them.
Aerosols (smaller than 100 micrometres, including the respirable fraction below 5 micrometres) are produced by breathing, talking, coughing and aerosol-generating procedures. They can stay suspended for minutes to hours and travel beyond 2 metres. Ventilation, air filtration and fit-tested P2 or N95 respirators address them.
Fomites: Respiratory secretions deposited on surfaces that are then transferred to mucous membranes via hand contact. Hand hygiene and environmental cleaning address them.
In poorly ventilated indoor spaces – typical of many aged care communal areas during winter – aerosols accumulate, increasing the probability of inhalation by susceptible residents and staff. Ventilation dilutes and removes these airborne particles, directly reducing infection risk.
What Is the Role of Ventilation in Reducing Airborne Transmission?
Ventilation reduces airborne transmission of respiratory infections by diluting infectious aerosols with clean outdoor air and removing contaminated air from indoor spaces. Higher ventilation rates correlate with lower infection transmission risk.
WHO guidance on natural ventilation for infection control in health-care settings (2009) describes an airborne precaution room as one with more than 12 air changes per hour (ACH). Other guidance uses 6 ACH as a general health care benchmark. Aged care is not classified as acute health care, so use these figures as a reference for outbreak planning rather than as a requirement for your building.
A systematic review by Li et al. (2007), published in Indoor Air, demonstrated that insufficient ventilation was associated with increased transmission of respiratory infections in buildings. Evidence from the COVID-19 pandemic strengthened the case that ventilation and air cleaning reduce indoor airborne transmission, although most studies are observational (Morawska et al., 2021).
How Does Natural Ventilation Work in Aged Care During Winter?
Natural ventilation Essentially, opening windows and doors to allow outdoor air to flow through indoor spaces is the simplest and most cost-effective ventilation strategy. However, natural ventilation during the Australian winter (June-August) creates a direct conflict between infection prevention and resident comfort.
Cold air discomfort: Aged care residents, particularly those with poor circulation, low body mass, or limited mobility, are highly sensitive to cold. Opening windows in winter can cause significant thermal discomfort, an increased risk of hypothermia, and resident complaints.
Practical strategies for winter natural ventilation: Open windows briefly and often (IPS suggested practice: 10-15 minutes every 1-2 hours) rather than leaving them open continuously, with window restrictors in place and residents kept warm. Cross-ventilate by opening windows on opposite sides of a room. Ventilate communal areas between activities (e.g., after meals, after group activities) when residents are not present.
Bedroom ventilation: Open resident bedroom windows during bed-making and room cleaning, then close before the resident returns. Even brief natural ventilation episodes significantly reduce aerosol concentration.
Common area rotation: Where possible, rotate residents between communal areas, ventilating empty rooms before re-occupation.
Need help implementing this in your facility? The IPS Hub gives your IPC Lead instant access to ready-made policies, procedures, and audit tools — updated monthly.
What Should Be Done with Mechanical Ventilation Systems Before Winter?
Mechanical ventilation systems (HVAC — heating, ventilation, and air conditioning) require pre-winter maintenance to ensure optimal performance during the peak infection season. HVAC systems that are poorly maintained may recirculate contaminated air, distribute pathogens between rooms, or fail to deliver adequate fresh air supply.
Pre-Winter HVAC Maintenance Checklist
Replace air filters according to manufacturer specifications. Use the highest-efficiency filters your system can handle without losing airflow (MERV 13 or equivalent, for example ISO 16890 ePM1), and confirm with your HVAC contractor.
Inspect and clean ductwork, paying particular attention to areas prone to moisture and microbial growth.
Verify that the system is delivering the designed proportion of outdoor air (not 100% recirculated air). Many HVAC systems have adjustable outdoor air dampers that may have been closed to reduce energy costs.
Commission an HVAC performance assessment to verify air changes per hour (ACH) in key areas: communal dining rooms, lounges, activity rooms, and corridors.
Check and clean heating components (heat exchangers, coils, drip trays) to prevent microbial contamination of heated air.
Document all maintenance activities in the facility’s planned preventive maintenance register.
How Can CO2 Monitoring Indicate Ventilation Adequacy?
CO2 monitoring is a practical, low-cost method of assessing ventilation adequacy in real time. Humans exhale CO2, so indoor CO2 concentration rises when ventilation is insufficient relative to occupancy. Because respiratory pathogens are also exhaled, CO2 levels serve as a proxy indicator for the accumulation of potentially infectious aerosols.
| CO2 Level (ppm) | Ventilation Assessment | Action Required |
|---|---|---|
| < 600 ppm | Excellent ventilation | Maintain current ventilation settings |
| 600-800 ppm | Acceptable ventilation | Monitor; no immediate action needed |
| 800-1,000 ppm | Marginal ventilation | Increase fresh air supply; open windows if safe; check HVAC outdoor air dampers |
| 1,000-1,500 ppm | Poor ventilation | Act now: open windows or increase outdoor air, check HVAC dampers, reduce numbers or time spent in the room. Portable HEPA purifiers help with particles but will not lower the CO2 reading. |
| > 1,500 ppm | Inadequate ventilation | Escalate to the IPC Lead and maintenance. Reduce occupancy or shorten the activity, and consider moving the activity to a better-ventilated area if that is safe and suits the residents. |
Outdoor CO2 levels are approximately 420 ppm (2024 global average). Indoor levels are always higher due to human exhalation. The bands in the table are IPS suggested action levels. CO2 readings are a guide only. They do not detect infectious particles and are less reliable when rooms are lightly occupied or portable air cleaners are in use (see the ABCB Indoor Air Quality Handbook, 2022, for the building-standard context).
Where Should CO2 Monitors Be Placed?
Communal dining rooms (where residents gather in close proximity during meals).
Lounge and activity rooms (prolonged occupancy, often with reduced ventilation in winter).
Staff break rooms (staff remove masks to eat, creating a transmission risk).
Corridors near resident rooms (to assess overall building ventilation performance.
Mount monitors at breathing height (1.0-1.5 metres) away from windows, doors, and HVAC vents to avoid misleading readings.
When Should Portable HEPA Air Purifiers Be Used?
Portable HEPA (High-Efficiency Particulate Air) air purifiers supplement, but do not replace, ventilation by filtering airborne particles from indoor air. True HEPA filters (H13 or H14 under EN 1822) capture at least 99.95% (H13) or 99.995% (H14) of particles at the most penetrating particle size, which is around 0.3 micrometres. Respiratory aerosols carrying virus are larger or smaller than this size and are captured effectively.
Where to Deploy HEPA Purifiers in Aged Care
Resident isolation rooms where increased ventilation via windows or HVAC is not achievable.
Communal areas where CO2 monitoring indicates marginal or poor ventilation (> 800 ppm).
During confirmed respiratory outbreaks, in all affected areas, as an additional layer of protection.
Staff break rooms where staff unmask to eat and drink.
How to Select and Size a HEPA Purifier
Select units with true HEPA filters (H13 or H14 grade). Avoid units marketed as ‘HEPA-like’ or ‘HEPA-type’ which do not meet the HEPA standard.
Size the purifier to the room volume: the unit should deliver a clean air delivery rate (CADR) sufficient to provide at least 5 equivalent air changes per hour (eACH) in the target room (a commonly used target, for example in CDC COVID-19 ventilation guidance). Check the CADR rating from a recognised test (for example AHAM or an equivalent), and consider noise and trip hazards from cords in residents’ rooms.
Calculation: Required CADR (m3/hour) = Room volume (m3) x Target eACH. For a 40 m2 room with 2.7 m ceiling height: 40 x 2.7 = 108 m3. At 5 eACH: 108 x 5 = 540 m3/hour CADR required.
Position purifiers to draw air from the breathing zone (mid-room placement preferred). Avoid placement in corners or behind furniture where airflow is obstructed.
Maintain HEPA purifiers according to the manufacturer’s instructions: filter replacement on schedule, pre-filter cleaning, unit inspection.
What Are the Air Changes Per Hour Recommendations?
Air changes per hour (ACH) is the measure of how many times the total volume of air in a room is replaced with fresh or filtered air in one hour. Higher ACH values correlate with greater dilution of airborne pathogens and lower infection risk.
| Setting | Reference benchmark | Source |
|---|---|---|
| General aged care residential areas | No specific ACH set for residential aged care; AS 1668.2 sets outdoor air rates per person | AS 1668.2-2012 |
| Aged care communal areas during outbreak | As high as practicable (IPS target: combined natural, mechanical and portable filtration) | IPS good practice |
| Isolation rooms for respiratory precautions (if available) | More than 12 ACH, with negative pressure | WHO (2009); Australasian Health Facility Guidelines Part D |
| Staff break rooms | As high as practicable | IPS good practice |
Most existing aged care buildings were not designed to achieve healthcare-level ACH. Facilities should commission a ventilation assessment to determine baseline ACH in key areas and develop a remediation plan for spaces that fall significantly below targets. Portable HEPA purifiers can bridge the gap by providing equivalent air changes.
How Can Facilities Balance Ventilation with Resident Thermal Comfort?
The tension between ventilation (requiring air exchange with cooler outdoor air) and thermal comfort (keeping residents warm) is the central practical challenge of winter ventilation in aged care. Older adults have reduced thermoregulatory capacity and are at risk of hypothermia, falls, and cardiovascular events when exposed to cold indoor temperatures.
Practical Strategies for Balancing Ventilation and Warmth
Use mechanical ventilation with heat recovery (MVHR) systems where installed, which extract stale air while recovering heat from the exhaust stream to pre-warm incoming fresh air.
Employ intermittent intensive ventilation (e.g., opening windows fully for 10-15 minutes between activities) rather than continuous low-level ventilation that creates constant draught.
Ensure residents are appropriately dressed in warm layers before ventilation events. Provide blankets in communal areas.
Use radiant heating (such as ceiling-mounted radiant panels) which warm occupants directly without heating the air, allowing ventilation without thermal penalty.
Monitor indoor temperatures alongside CO2. Keep rooms at a temperature that is comfortable for residents, and agree a target range in your own policy, taking resident preferences and local guidance into account.
Prioritise HEPA air purifiers in rooms where opening a window creates unacceptable cold; the purifier provides equivalent infection-risk reduction without a temperature drop.
What Ventilation Strategies Apply During Outbreaks?
During active respiratory outbreaks, ventilation must be escalated to reduce the concentration of infectious aerosols in the facility. Enhanced ventilation during outbreaks is a complement to, not a substitute for, PPE, cohorting, and other transmission-based precautions.
Increase ACH in affected areas to the maximum achievable level through combined natural, mechanical, and portable HEPA filtration.
If the HVAC system serves multiple zones, verify that recirculated air from the outbreak zone is not being distributed to unaffected areas. Close the interconnecting dampers if possible or set the system to 100% outdoor-air mode. Deploy portable HEPA purifiers in isolation rooms, cohort zones, and corridors adjacent to outbreak areas.
If a negative pressure room is available, use it for residents with infections that need respiratory precautions with a P2/N95 respirator, such as pulmonary tuberculosis. For COVID-19, follow current national and state guidance on when a P2/N95 respirator and negative pressure are needed, for example during aerosol-generating procedures. For routine outbreak cohorting, enhanced ventilation is recommended but negative pressure is not universally required. Verify negative pressure with smoke testing or differential pressure monitoring.
Open windows in outbreak areas more often and for longer, as a temporary measure, when residents are out of the room or well covered. Check that window restrictors are in place, that no resident is at risk of a fall or of leaving the building, and that bedbound residents are kept warm. Provide extra heating and blankets to offset cold.
Related: Winter Preparedness for Infection Prevention in Aged Care
Related: Environmental Cleaning in Aged Care
What Are the Relevant Australian Standards for Ventilation?
Several Australian and international standards are relevant to ventilation for infection prevention in aged care, although no single standard specifically addresses ventilation requirements in residential aged care facilities.
| Standard | Scope | Relevance to Aged Care |
|---|---|---|
| AS 1668.2-2012 | Use of ventilation and air conditioning in buildings — ventilation design for indoor air quality | Sets minimum outdoor air requirements for various building types; applicable where aged care is classified as an assembly or institutional occupancy |
| AS/NZS 3666.1-2011 | Air-handling and water systems of buildings — microbial control | Covers microbial control of air-handling and water systems: design, installation, commissioning and maintenance |
| National Construction Code (NCC) 2022 | Building requirements for ventilation in residential and healthcare buildings | Sets minimum ventilation provisions for new builds and major renovations; older aged care buildings may pre-date current requirements |
| WHO Roadmap to Improve Ventilation (2021) | Global guidance on ventilation for infection control in buildings | Global guidance on improving ventilation in buildings, including health care and congregate settings (2021); offers practical strategies that can be adapted to aged care |
Frequently Asked Questions
What CO2 level indicates poor ventilation in aged care?
A CO2 level above 800 ppm in an occupied communal area indicates that ventilation may be insufficient relative to the occupancy level. Levels above 1,000 ppm need prompt action: increase fresh air supply or reduce room occupancy. Portable HEPA purifiers help with particles but will not lower the CO2 reading. Levels above 1,500 ppm indicate inadequate ventilation. Escalate to your IPC Lead and maintenance team, and reduce occupancy or move the activity if it is safe and suitable for residents.
Are HEPA air purifiers effective against COVID-19 and influenza?
Yes. Portable HEPA purifiers remove respiratory aerosols from room air. H13 filters capture at least 99.95% and H14 at least 99.995% of particles at the most penetrating particle size (about 0.3 µm), per EN 1822. Studies of portable HEPA purifiers in classrooms have shown large falls in airborne particle levels, depending on unit size, room size and placement. In one German classroom study, purifiers delivering 5.5 air changes per hour cut particle levels by more than 90% within 30 minutes (Curtius et al., 2021, Aerosol Science and Technology). HEPA purifiers are most effective when correctly sized to the room volume and positioned in the breathing zone.
How often should HVAC filters be changed in aged care?
HVAC filters should be changed according to manufacturer specifications, as the manufacturer and HVAC contractor specify; intervals vary with filter grade and dust load. Before winter, filters should be replaced regardless of the scheduled change date to ensure optimal performance during the peak infection season. Facilities should maintain a stock of replacement filters on-site.
Can opening windows in winter really reduce infection risk?
Yes. Even brief episodes of window opening (10-15 minutes) significantly reduce indoor aerosol concentration by introducing fresh outdoor air that dilutes infectious particles. Natural ventilation can deliver high air-change rates, as shown in naturally ventilated hospital rooms in Peru (Escombe et al., 2007, PLoS Medicine). That study was in a warm climate, so the benefit in cold weather has to be balanced against resident comfort. The key is to ventilate intensively and briefly between activities, rather than leaving windows open continuously and creating thermal discomfort.
Do aged care facilities need negative pressure rooms?
Negative pressure rooms are not a regulatory requirement for residential aged care facilities in Australia. However, facilities that may need to manage residents who require respiratory precautions with a P2/N95 respirator (such as pulmonary tuberculosis) benefit from knowing where the nearest negative pressure room is, which is usually in a hospital. Residential aged care facilities rarely have one. For most aged care settings, the combination of mechanical ventilation, natural ventilation, and portable HEPA purifiers provides adequate airborne infection control.
References and Further Reading
The following authoritative sources inform the clinical and regulatory guidance in this article. Links open in a new tab.
- World Health Organization. (2009). Natural ventilation for infection control in health-care settings. Geneva: WHO.
- World Health Organization. (2021). Roadmap to improve and ensure good indoor ventilation in the context of COVID-19. Geneva: WHO.
- Li, Y., et al. (2007). Role of ventilation in airborne transmission of infectious agents in the built environment: A multidisciplinary systematic review. Indoor Air, 17(1), 2-18.
- Morawska, L., et al. (2021). A paradigm shift to combat indoor respiratory infection. Science, 372(6543), 689-691.
- Escombe, A. R., et al. (2007). Natural ventilation for the prevention of airborne contagion. PLoS Medicine, 4(2), e68.
- Curtius, J., Granzin, M., & Schrod, J. (2021). Testing mobile air purifiers in a school classroom: Reducing the airborne transmission risk for SARS-CoV-2. Aerosol Science and Technology, 55(5), 586-599.
- Australian Building Codes Board. (2022). Indoor air quality handbook.
- Aged Care Quality and Safety Commission. (2025). Strengthened Aged Care Quality Standards.
- Standards Australia. (2012). AS 1668.2-2012 The use of ventilation and airconditioning in buildings, Part 2: Mechanical ventilation in buildings.
- Standards Australia & Standards New Zealand. (2011). AS/NZS 3666.1:2011 Air-handling and water systems of buildings: Microbial control: Design, installation and commissioning.
In This Article
- How Do Respiratory Infections Spread via Aerosols and Droplets?
- What Is the Role of Ventilation in Reducing Airborne Transmission?
- How Does Natural Ventilation Work in Aged Care During Winter?
- What Should Be Done with Mechanical Ventilation Systems Before Winter?
- How Can CO2 Monitoring Indicate Ventilation Adequacy?
- When Should Portable HEPA Air Purifiers Be Used?
- What Are the Air Changes Per Hour Recommendations?
- How Can Facilities Balance Ventilation with Resident Thermal Comfort?
- What Ventilation Strategies Apply During Outbreaks?
- What Are the Relevant Australian Standards for Ventilation?
- Frequently Asked Questions

About the Author
Lyndon Forrest is the Managing Director of Bug Control — Infection Prevention Services, with over 30 years’ experience supporting aged care facilities across Australia and New Zealand with infection prevention, antimicrobial stewardship, and accreditation readiness.
Clinically reviewed by Bridgette Mackie & Dianne Newey, Clinical Directors.
Ready to Strengthen Your Facility’s Infection Prevention?
The IPS Hub provides aged care facilities across Australia and New Zealand with continuously updated IPC policies, AMS tools, outbreak management resources, and direct support from experienced IPC professionals.


